Buy Metravi ZNT-34 Relay Test Set online at best price in India. Fault phase voltage adjustable between 0 to 110%. Fault current adjustable between 0 to 100%. Genuine Metravi product, GST invoice & fast delivery.
₹4,05,000₹2,83,20030% off
Inclusive of GST · You save ₹1,21,800 · GST invoice available
Designed for accuracy you can trust, the Metravi ZNT-34 Relay Test Set is a professional-grade relay test set from Metravi suited to both field and bench applications. Widely used by electricians, electrical contractors, maintenance engineers and industrial plants, this relay test set is ideal for electrical installation testing, preventive maintenance, panel troubleshooting and safety compliance checks.
Key Features of Metravi ZNT-34 Relay Test Set
Fault phase voltage adjustable between 0 to 110%
Fault current adjustable between 0 to 100%
Phase angle adjustment & measurement 0° to 360°
Digital time interval meter.
Voltage & current indications by digital meters.
It is suitable for testing distance relays.
Other relays like over current, over voltage, under voltage, earth fault and relays having directional element can also be tested by this relay test set.
Input Voltage: 415V+/-10%, 3phase, 4 wire 50HZ AC
Test Voltages: AC Voltage source: 0-220 volts , phase to neutral, 50 HZ AC.
Rated maximum burden : 150VA / phase.
DC voltage source: Isolated 0-240 volts D.C. with maximum capacity available 1A.
Phase Angle Variation: 0 to 3600 in current ckt.
Applications
The Metravi ZNT-34 Relay Test Set is trusted by electricians, electrical contractors, maintenance engineers and industrial plants for electrical installation testing, preventive maintenance, panel troubleshooting and safety compliance checks.
Why Buy the Metravi Relay Test Set from Anand Syndicats?
Get the Metravi ZNT-34 Relay Test Set from Anand Syndicats with assured authenticity, competitive pricing, GST billing and quick nationwide delivery.
Specification
Overview
Brand
Metravi
Input Voltage Output (s)
415V +/- 10%, 3phase, 4 wire 50HZ AC.
[a] Test Current
0 to 1, 5, 10, 25A, 50A having 0 to 100% regulation in each tap & each phase.
Rated maximum burden
500 VA.per phase.
Duty Cycle: i)
continuous upto 10A. ii) 25A & 50A outputs are rated for intermittent duty cycle i.e. 5mins "ON", 10mins" OFF ".
[b] Test Voltages AC Voltage source
0-220 volts, phase to neutral, 50 HZ AC.
Fixed DC voltage source
Isolated fixed 30V/110V/220V DC of 100VA, with out metering
[c] Phase Angle Variation
0 to 360° in current ckt.
[d] Time Measurement
0-9.999 secs.& 0-99.99secs in two selectable ranges
Reviews
There are no reviews yet.